Enerzone Solution 3.4 Specifiche Pagina 35

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 52
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 34
Solution3.4InstallationandOperationManual
35
8.2.2 MASONRYFLUESYSTEMS
The wood fire may also be connected
to a masonry flue system, provided
the flue system complies with AS/NZS
2918 or with the construction rules
found in the building code enforced
locally. The flue system must have
either a clay liner or a suitably listed
stainless steel liner. If the masonry
flue system has a square or
rectangularliner thatis larger in cross
sectional area than a round 150 mm
(6”) flue, it should be relined with a
suitably listed 150 mm (6”) stainless
steelliner.Donotdownsizetheflueto
less than 150 mm (6”) unless the flue
systemisstraightandexceeds8m(25
feet) in height. Whenpassing through
a combustible wall, the use of an
insulatedlistedthimbleisrequired.
8.3 MINIMUMFLUESYSTEMHEIGHT
FlueheightsandlengthsfromAS/NZS2918:2001
Vedere la pagina 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 51 52

Commenti su questo manuale

Nessun commento